Design and characterization of a sealed hybrid-cooled high performance computing server

Abstract

This paper presents a novel 1U sealed design of high performances compute server using of jet impingement liquid cooling to cool the high power density components (CPU and GPUs. The system is studied using CFD simulations of both the liquid coolant loop and the recirculated air used to cool the peripheral components, showing good agreement with the experimental results with 52°C above ambient temperature measured on the CPU for the experimental data, versus 47°C for the simulation, and 22°C versus 16°C for the GPU core. Traditionally cooled HPC servers typically take a 2U or 4U form in order to accommodate the large liquid-air heat exchangers required to expel CPU and GPU heat into the air, however, this paper shows that this can be achieved in the significantly smaller 1 U form factor by using a sealed server architecture.

Authors

Lebon M; Battaglioli S; Jenkins R; Parry I; Robinson AJ

Volume

00

Pagination

pp. 1-4

Publisher

Institute of Electrical and Electronics Engineers (IEEE)

Publication Date

January 30, 2022

DOI

10.1109/therminic57263.2022.9950654

Name of conference

2022 28th International Workshop on Thermal Investigations of ICs and Systems (THERMINIC)
View published work (Non-McMaster Users)