Home
Scholarly Works
Seismic Response of High Voltage Electrical...
Journal article

Seismic Response of High Voltage Electrical Transformer–Bushing Systems

Abstract

High voltage porcelain bushings mounted on transformers have shown vulnerability during past earthquakes. This is contrary to the generally good performance observed during shake table qualification testing of bushings anchored to a rigid base. The seismic vulnerability of porcelain bushings might be caused by the flexibility of transformer tanks and of bushing attachments. Current seismic qualification guidelines consider an amplification factor of 2.0 between the amplitude of the ground motion and the amplitude of the motion at the base of the bushing. This paper investigates numerically the dynamic response of porcelain bushings mounted on transformer tanks. The results of the numerical study show that large amplification occurs when the fundamental frequency of the porcelain bushing is tuned with the fundamental frequency of the transformer tank.

Authors

Filiatrault A; Matt H

Journal

Journal of Structural Engineering, Vol. 132, No. 2, pp. 287–295

Publisher

American Society of Civil Engineers (ASCE)

Publication Date

February 1, 2006

DOI

10.1061/(asce)0733-9445(2006)132:2(287)

ISSN

0733-9445