Abstract

The DC reactor is an important piece of equipment for restraining loop and ripple currents in the international thermonuclear experimental reactor (ITER) converter power supply system. As the reactor is operated at a steady state of 27.5 kA and needs to withstand a peak current of 175 kA, so the design of the DC reactor used in the ITER converter power supply system is necessary. A new water-cooling dry-type air-core reactor is designed in this work. The detailed structural parameters are calculated by theoretical formulas, and then the structure is optimized by electromagnetic simulation with ANSYS. Finally, thermal and dynamic stability analyses are performed to verify the temperature and stress at a rated current of 27.5 kA and pulsed current of 175 kA. The analysis results show that the temperature and stress meet the requirements of the ITER converter power supply system.

Authors

Yang N; Zhang M; Li C; Song Z; Yu K; Zhuang G; Xu T

Journal

Plasma Science and Technology, Vol. 16, No. 3, pp. 273–277

Publisher

IOP Publishing

Publication Date

March 1, 2014

DOI

10.1088/1009-0630/16/3/18

ISSN

1009-0630