Home
Scholarly Works
Effects of harmonics on converter transformer load...
Journal article

Effects of harmonics on converter transformer load losses

Abstract

Losses were measured during short-circuit tests on a 262.5 MVA, three-phase, five limb converter transformer at various frequencies from 50 Hz to 1 KHz. Using these and the calculated values of the harmonic currents produced by the AC/DC converter, load losses were determined. Variations of these losses with the converter firing angle, with the transformer reactance and with the load were studied. A simple method of loss calculation which has the potential for application at the design stage was developed.<>

Authors

Ram BS; Forrest JAC; Swift GW

Journal

IEEE Transactions on Power Delivery, Vol. 3, No. 3, pp. 1059–1066

Publisher

Institute of Electrical and Electronics Engineers (IEEE)

Publication Date

July 1, 1988

DOI

10.1109/61.193887

ISSN

0885-8977

Contact the Experts team